Analog Input Unit (4-channel) KV-RC4AD

KV-RC4AD - Analog Input Unit (4-channel)

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-RC4AD

General specifications

Vibration resistance

Intermittent vibration

Frequency:5 to 9Hz

Half amplitude: 3.5 mm*1

Frequency:9 to 150Hz

Acceleration: 9.8 m/s2*1

Continuous Vibration

Frequency:5 to 9Hz

Half amplitude: 1.75 mm*1

Frequency:9 to 150Hz

Acceleration: 4.9 m/s2*1

Current consumption

210mA

Power voltage

24 VDC ± 10%

Operating ambient temperature

0 to +60°C (no freezing)

Operating ambient humidity

10 to 95%RH(no condensation)

Ambient temperature for storage

-20 to +75°C

Approved standards

Overvoltage category

I

Pollution degree

2

Storage relative humidity

10 to 95%RH(no condensation)

Approved standards

CE marking

EMI :EN55011 Class A
EMS :EN61131-2

Operating environment

Minimal amount of dust and corrosive gas present

Altitude

2000m or less

Approved standards

FCC

FCC Part15B class A

UL

UL :UL508
CSA :CAN/CSA22、2 No.14

ICES

ICES-003 Issue4

Noise immunity

1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by way of a noise simulator), conforms to IEC standards (IEC 61131-2)

Withstand voltage

1,500 VAC for 1 minute (between the power supply terminal and the communication terminal, between the power supply terminal and the I/O terminals, and between all the external terminals and the case)

Enclosure rating

IP2X

Insulation resistance

50 MΩ or more (tested with a 500 VDC megger, between the power supply terminal and the I/O terminal)

CC-Link specifications

Supported versions: 2.00, 1.10; number of occupied stations: 1 station ×2 with version 2.00, 2 stations with version 1.10; station type: remote device station

Performance specifications

Conversion speed

200 µs/ch

Conversion precision

Voltage: ±0.2% of F.S. at 25°C ± 5°C, voltage: ±0.2% of F.S. between 0 and 60°C, current: ±0.2% of F.S. at 25°C ± 5°C, current: ±0.2% of F.S. between 0 and 60°C

Isolation mode

Photocoupler, non-isolated channels

Analog input, general-purpose I/O specifications

Analog input range (resolution)

Voltage: -10 to 10 V (0.83 mV, 1/24000), 0 to 10 V (0.83 mV, 1/12000), -5 to 5 V (0.42 mV, 1/24000), 0 to 5 V (0.42 mV, 1/12000), 1 to 5 V (0.42 mV, 1/9600); current: 0 to 20 mA (1.67 µA, 1/12000), 4 to 20 mA (1.67 µA, 1/9600)Inputs:
Voltage: -10 to 10 V (0.83 mV, 1/24000), 0 to 10 V (0.83 mV, 1/12000), -5 to 5 V (0.42 mV, 1/24000), 0 to 5 V (0.42 mV, 1/12000), 1 to 5 V (0.42 mV, 1/9600); current: 0 to 20 mA (1.67 µA, 1/12000), 4 to 20 mA (1.67 µA, 1/9600)
Output: -

Number of analog inputs

4Inputs: 4, Output: -

Performance specifications

Input resistance

Voltage: 1 MΩ,*2 current: 250 Ω

Analog input, general-purpose I/O specifications

Input method

Differential input

Performance specifications

Absolute max. input

Voltage: ±15 V, current: 30 mA

Analog input, general-purpose I/O specifications

General-purpose (trigger) input

Input signal: NPN open collector No-voltage contact signal Maximum voltage when product turned on: 0.8 V or less Maximum current when product turned off: 0.1 mA or less Isolation method: photocoupler isolation

General purposeoutput

Output format: transistor (NPN) Rated load: 24 VDC, 0.5 A Leakage current when product turned off: 100 µA or less Residual voltage when product turned on: 0.8 V or less Response time: 20 µs or less when switched from off to on, 200 µs or less when switched from on to off Isolation method: photocoupler isolation

Weight

approx 200g

*1 Conforms to JIS B 3502 IEC61131-2
Number of sweeps: 10 times respectively in the X, Y, and Z directions, 100 minutes
*2 500 kΩ when the common is used