Analog Output Unit (4-channel) KV-RC4DA

KV-RC4DA - Analog Output Unit (4-channel)

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-RC4DA

General specifications

Vibration resistance

Intermittent vibration

Frequency:5 to 9Hz

Half amplitude: 3.5 mm*1

Frequency:9 to 150Hz

Acceleration: 9.8 m/s2*1

Continuous Vibration

Frequency:5 to 9Hz

Half amplitude: 1.75 mm*1

Frequency:9 to 150Hz

Acceleration: 4.9 m/s2*1

Current consumption

240mA

Power voltage

24 VDC ± 10%

Operating ambient temperature

0 to +60°C (no freezing)

Operating ambient humidity

10 to 95%RH(no condensation)

Ambient temperature for storage

-20 to +75°C

Approved standards

Overvoltage category

I

Pollution degree

2

Storage relative humidity

10 to 95%RH(no condensation)

Approved standards

CE marking

EMI :EN55011 Class A
EMS :EN61131-2

Operating environment

Minimal amount of dust and corrosive gas present

Altitude

2000m or less

Approved standards

FCC

FCC Part15B class A

UL

UL :UL508
CSA :CAN/CSA22、2 No.14

ICES

ICES-003 Issue4

Noise immunity

1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by way of a noise simulator), conforms to IEC standards (IEC 61131-2)

Withstand voltage

1,500 VAC for 1 minute (between the power supply terminal and the communication terminal, between the power supply terminal and the I/O terminals, and between all the external terminals and the case)

Enclosure rating

IP2X

Insulation resistance

50 MΩ or more (tested with a 500 VDC megger, between the power supply terminal and the I/O terminal)

CC-Link specifications

Supported versions: 2.00, 1.10; number of occupied stations: 1 station ×2 with version 2.00, 2 stations with version 1.10; station type: remote device station

Performance specifications

Analogue output range (resolution)

Voltage: -10 to 10 V (0.83 mV, 1/24000)
0 to 10 V (0.83 mV, 1/12000)
-5 to 5 V (0.42 mV, 1/24000)
0 to 5 V (0.42 mV, 1/12000)
1 to 5 V (0.42 mV, 1/9600)
current: 0 to 20 mA (1.67 µA, 1/12000)
4 to 20 mA (1.67 µA, 1/9600)

Conversion speed

-

Conversion precision

Isolation mode

Number of analog outputs

4

Minimum load resistance

Voltage: 1 kΩ

Maximum load resistance

Current: 400 Ω

Weight

approx 200g

*1 Conforms to JIS B 3502 IEC61131-2
Number of sweeps: 10 times respectively in the X, Y, and Z directions, 100 minutes

Data Sheet (PDF) Other Models