Recent Searches
    Series ()
      Models ()
        Keywords

          Touch Panel DisplayVT3 series

          VT-T1

          Removable Relay Terminal Block Unit

          SPECIFICATIONS

          Select Language

          Model

          VT-T1

          General specifications

          Current consumption

          VT-T1: 50 mA or less, VT3-V6H (G) + VT-T1: 430 mA or less, VT3-Q5H (G) + VT-T1: 300 mA or less

          Structure

          Panel-mount type (Only the front part. When checking the connectors, the construction has dustproofing and splashproofing equivalent to IP65f.) and DIN-mount type

          Overvoltage category

          I

          Pollution degree

          3

          Power voltage

          24 VDC ±10%

          Noise resistance

          1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by way of a noise simulator)

          Withstand voltage

          1500 VAC 1 minute (between power terminal and housing)

          Insulation resistance

          50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing)

          Vibration resistance

          Intermittent vibration

          Frequency: 5 to 9 Hz

          Half amplitude: 3.5 mm*1

          Frequency: 9 to 150 Hz

          Acceleration: 9.8 m/s2*1

          Continuous vibration

          Frequency: 5 to 9 Hz

          Half amplitude: 1.75 mm*1

          Frequency: 9 to 150 Hz

          Acceleration: 4.9 m/s2 *1

          Ground

          Class D grounding
          (Class 3 grounding).

          Operating environment

          Minimal amount of dust and corrosive gas present

          Ambient operating temperature

          0 to +50°C

          Ambient operating humidity

          35 to 85%RH (No condensation)*2

          Ambient storage temperature

          -10 to +60°C (No freezing)

          Ambient storage humidity

          35 to 85%RH (No condensation)*2

          Weight

          Approx 410 g

          Performance specifications

          Can be used to enable and disable the emergency stop push-button switch

          A key switch can be used to enable and disable the emergency stop pushbutton switch.

          Power supply ON/OFF switching

          A key switch can be used to turn the power supply to the VT3 handy series on and off.

          Cable wiring terminal block conversion

          Cable wiring has been changed to a terminal block.

          I/O specifications

          PLC communication cable connection connector

          Applied standard

          Conforms to EIA RS-232C and RS-422

          Synchronization between the transmitter and receiver

          Start-stop, full duplex

          Communication distance

          15m (RS-232C)/500m (RS-422)*3

          Data length

          7 or 8 bits

          Parity

          Even, odd, none

          Communication speed

          1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps

          Ethernet connector

          Compliance

          IEEE802.3

          Transmission speed

          10 Mbps (10BASE-T),100 Mbps (100BASE-TX)

          Transmission medium

          STP or category 3 or higher UTP (10BASE-T), STP or category 5 or higher UTP (100BASE-TX)*4

          Maximum cable length

          100 m*5

          Maximum number of connectable hubs

          4 (10BASE-T),2 (100BASE-TX)

          Maximum number of connections

          PC application:*6 3,
          FTP: 4

          MegaLink (A/B/G)

          Applied standard

          RS-485

          Synchronization between the transmitter and receiver

          Start-stop, half duplex

          Communication speed

          19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps

          Cable connection

          Multi-drop (branching is not possible)

          Maximum number of connectable units

          15

          Baud rate 19200

          Maximum extension distance: 1,000 m*5

          Baud rate 115200

          Baud rate 0.5 M

          Maximum extension distance: 500 m*5

          Baud rate 1 M

          Maximum extension distance: 200 m*5

          Baud rate 2 M

          Maximum extension distance: 100 m*5

          VT2 multi-link (A/B/G)

          Applied standard

          RS-485

          Synchronization between the transmitter and receiver

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m*5

          Communication speed

          19200, 115200, 0.5M, 1M bit/s

          Baud rate 115200 or less

          Maximum extension distance: 500 m*5

          Baud rate 0.5 M

          Maximum extension distance: 100 m*5

          Baud rate 1 M

          Maximum extension distance: 50 m*5

          Multi-link (A/B/G)

          Applied standard

          RS-485

          Synchronization between the transmitter and receiver

          Start-stop, half duplex

          Communication distance

          Maximum extension distance: 500 m*5

          Communication speed

          19200, 38400, 57600, 115200 bit/s

          Emergency stop push-button switch monitor (TPAM/TPBM)

          Rated voltage

          30 VDC

          Rated current

          1 A (resistive load)

          Contact method

          1a contact

          Durability

          Mechanical

          50,000,000 times or more

          Electrical

          100,000 times or more

          Key switch monitor (TKAM/TKBM)

          Rated voltage

          30 VDC

          Rated current

          1 A (resistive load)

          Contact method

          1a contact

          Durability

          Mechanical

          20,000,000 times or more

          Electrical

          100,000 times or more

          *1 Conforms to JIS B 3502, IEC61131-2
          Number of sweeps: 10 times respectively in the X, Y, and Z directions (100 minutes)
          *2 When the ambient temperature is higher than 40°C, please use it in the condition of an absolute humidity of 85%RH at 40°C.
          *3 Maximum extension distance also includes the length of the cable between the VT3-V6H (G)/Q5H (G) and the VT-T1.
          *4 STP = shielded twisted pair cable, UTP = unshielded twisted pair cable
          *5 This also includes the length of the cable between the VT3-V6H (G)/Q5H (G) and the VT-T1.