Ultra-compact building-type PLC
KZ-300/350 series
Recommended Replaceable Products: CPU unit with built-in EtherNet/IP™ port - KV-7500
Contact Us: 1-800-88-1358 Enquiry form
CPU Unit, 10 Inputs, 4 Transistor (Sink) Outputs KZ-350
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model | KZ-350 | |||
Input unit | Input mode | 24 VDC input mode, 5 VDC input mode | ||
Input maximum rating | 26.4 VDC | |||
Input voltage | 24 VDC, 5.3 mA (24 VDC input mode); 5 VDC, 1 mA (5 VDC input mode) | |||
Minimum ON voltage | 19 V (24 VDC input mode), 3.5 V (5 VDC input mode) | |||
Maximum OFF current | 1.5mA | |||
Maximum OFF voltage | 1.5 V (5 VDC input mode) | |||
Common ground | 10/common | |||
Input time constant | 10 ms ± 20%, 25 µs ± 20%, 25 µs ± 20%, 10 µs ± 20% (shared between OFF to ON and ON to OFF) | |||
Output unit | Output | Transistor (NPN) | ||
Rated load | 30VDC 0.1A | |||
Leakage current (at OFF) | 100 µA or less | |||
Residual voltage (at ON) | 0.3V or less | |||
Operating time | 10 µs or less (shared between ON to OFF and OFF to ON) | |||
Common ground | 4/common | |||
Environmental resistance | Insulation resistance | 50 MΩ | ||
Ambient temperature | 0 to +50 °C (No freezing) | |||
Relative humidity | 35 to 85 % RH (No condensation) | |||
Withstand voltage | 1,500 VAC for 1 minute | |||
Noise resistance | 1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by way of a noise simulator) | |||
Operating environment | No corrosive gas present | |||
Vibration resistance | 10 to 55 Hz, Double amplitude 1.5 mm or less, 2 hours in each of the X, Y, and Z directions |