Programmable Controller
KV-5000/3000 series
Recommended Replaceable Products: 64-point Connector - KV-C64XC
Contact Us: 1-800-88-1358 Enquiry form
64-point Connector KV-C64XA
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model | KV-C64XA | |||
Type | Input unit | |||
External connection mode | Connector (MIL standard)*1 | |||
Input | Number of inputs | 64 points | ||
Input mode | DC 24 V mode (2-wire compatible)*2, DC 24 V mode (not 2-wire compatible)*3 | |||
Max. input voltage | DC 26.4 V (±10 %) | |||
Rated input voltage | DC 24 V mode (2-wire compatible): DC 24 V, 5.3 mA | |||
Min. ON voltage | 19 V | |||
Max. OFF current | DC 24 V mode (2-wire compatible): 1.5 mA | |||
Common point mode | 32 points/1 common (4 terminals)*4 | |||
Input time constant | [Constant at input setting 25µs] OFF to ON: TYP 25 µs/MAX 65 µs、ON to OFF: TYP 75 µs/MAX 120 µs | |||
Input impedance | DC 24 V mode (2-wire compatible): 4.3 kΩ | |||
Internal current consumption | 25 mA or less | |||
Weight | Approx. 140 g | |||
*1 In conformity with MIL-C-83503. |